Energy Recovery Wheel Troubleshooting: Common Faults and Fixes

Low effectiveness Cause: wheel not rotating (motor or belt failure), or condensate/fouling blocking the matrix.Fix: verify rotation and speed; wash the wheel with low-pressure water and a mild detergent; confirm belt tension. Frost or ice buildup (cold climates) Cause: exhaust-side temperature dropping below freezing.Fix: enable purge sector, reduce speed, or add preheat. See frost protection […]

Heat Exchanger Selection by Climate: Cold, Temperate, Hot-Humid

Cold climates (heating-dominated) Long, sub-zero winters make frost the enemy. Rotary wheels need purge sectors and occasional defrost; plate exchangers need bypass or preheat. Frost protection strategies are mandatory. Sensible-only recovery is usually enough because winter air is dry. Temperate climates Mild seasons with both heating and cooling loads favor balanced, all-season recovery. Plate and […]

AHU Heat Recovery Selection Calculation: A Step-by-Step Method

Step 1 – Known airflow Start with the supply/exhaust airflow Q (m3/h). For balanced AHUs, Q_supply approx Q_exhaust. Step 2 – Temperature difference Find the outdoor design temperature T_out and the exhaust (room return) temperature T_exp. The available temperature lift is DeltaT = T_exp – T_out. Step 3 – Effectiveness Choose an effectiveness epsilon (typical […]