Energy Recovery Wheel Troubleshooting: Common Faults and Fixes

Low effectiveness Cause: wheel not rotating (motor or belt failure), or condensate/fouling blocking the matrix.Fix: verify rotation and speed; wash the wheel with low-pressure water and a mild detergent; confirm belt tension. Frost or ice buildup (cold climates) Cause: exhaust-side temperature dropping below freezing.Fix: enable purge sector, reduce speed, or add preheat. See frost protection […]

Heat Exchanger Selection by Climate: Cold, Temperate, Hot-Humid

Cold climates (heating-dominated) Long, sub-zero winters make frost the enemy. Rotary wheels need purge sectors and occasional defrost; plate exchangers need bypass or preheat. Frost protection strategies are mandatory. Sensible-only recovery is usually enough because winter air is dry. Temperate climates Mild seasons with both heating and cooling loads favor balanced, all-season recovery. Plate and […]

Heat Exchanger Selection by Application: Hospital, Data Center, Food Plant

One device, many jobs Air-to-air heat recovery is applied across very different buildings, and the “best” exchanger depends on what each building values most: air purity, uptime, moisture control, or simply first cost. Below are three common sectors and the logic that drives their choice. Hospitals Air quality is non-negotiable. Fresh-air volumes are huge and […]

AHU Heat Recovery Selection Calculation: A Step-by-Step Method

Step 1 – Known airflow Start with the supply/exhaust airflow Q (m3/h). For balanced AHUs, Q_supply approx Q_exhaust. Step 2 – Temperature difference Find the outdoor design temperature T_out and the exhaust (room return) temperature T_exp. The available temperature lift is DeltaT = T_exp – T_out. Step 3 – Effectiveness Choose an effectiveness epsilon (typical […]

Plate vs Rotary vs Heat Pipe: How to Choose a Heat Exchanger

Choosing the right air-to-air heat exchanger depends on airflow, temperature, humidity, installation space, and contamination risk. This guide compares the three most common technologies. Quick Comparison Feature Plate Exchanger Rotary Wheel Heat Pipe Efficiency High (70–85 %) High (75–85 %) Moderate (50–70 %) Moving parts None Motor/bearings None Cross-contamination Very low Low with purge Zero […]