Heat Recovery Effectiveness Test Standards

“Effectiveness” is the number every code and rating system quotes, but the value only means something if the test method is stated. This article maps the main heat recovery effectiveness test standards and how they define the metric.

Definitions

  • Eficacia sensible ηs = (Tsupply − Toutdoor) / (Textract − Toutdoor).
  • Enthalpy (total) effectiveness ηt = (hsupply − houtdoor) / (hextract − houtdoor), using moist-air enthalpy.
  • Latent effectiveness uses humidity ratio in place of enthalpy.

The Standards

Standard Scope
EN 308 Test procedures for air-to-air and flue-gas heat recovery devices (sensible and latent).
EN 13053 Rating and performance of air-handling units, including heat recovery sections and pressure drop.
EN 13141-7 Performance testing of residential mechanical supply/exhaust ventilation units.
AHRI 1060 / 1061 Energy recovery ventilators — the method ASHRAE 90.1 references for its 50% minimum.

Why the Method Matters

  • Test conditions differ: Ecodesign measures ηt at −10 °C, 0 °C, and +10 °C outdoor; ASHRAE uses design heating and cooling conditions.
  • A wheel rated 75% by AHRI 1060 may read differently under EN 308 because of how leakage and frost are handled.
  • Pressure drop is part of the story — a more effective core that needs a bigger fan can erase the saving, which is why Ecodesign SFP limits bind efficiency and fan power together.

Picking a Device Against the Numbers

Use the measured ηt from the relevant standard when checking code floors. For non-rotating critical ventilation, compare a membrane core against a wheel on the same test basis, and fold the pressure drop into the AHU selection calculation.

Preguntas frecuentes

What is sensible effectiveness?
The ratio of temperature change delivered to the supply air versus the temperature difference between extract and outdoor air.

What is enthalpy effectiveness?
The same ratio using moist-air enthalpy, capturing both temperature and humidity recovery.

Which standards govern recovery testing?
EN 308, EN 13053, and EN 13141-7 in Europe, and AHRI 1060 and 1061 referenced by ASHRAE 90.1.

Why does the test method matter?
Different standards use different conditions and treat leakage and frost differently, so the same device can read differently, and pressure drop must also be considered.

Preguntas frecuentes

What is sensible effectiveness?

The ratio of temperature change delivered to the supply air versus the temperature difference between extract and outdoor air.

What is enthalpy effectiveness?

The same ratio using moist-air enthalpy, capturing both temperature and humidity recovery.

Which standards govern recovery testing?

EN 308, EN 13053, and EN 13141-7 in Europe, and AHRI 1060 and 1061 referenced by ASHRAE 90.1.

Why does the test method matter?

Different standards use different conditions and treat leakage and frost differently, so the same device can read differently, and pressure drop must also be considered.

Especifique el intercambiador adecuado

Nuestros ingenieros dimensionan el núcleo según su caudal, temperatura y presupuesto de caída de presión, y seleccionan recuperación por placa, rotativa o caloduc según la aplicación. Lea la guía del intercambiador , o contáctenos para una especificación.

Solicitar cotización

Productos relacionados

Air-to-Air Heat Exchanger

Recuperación por placa, rotativa o caloduc para HVAC y ventilación.

Plate Heat Exchanger

Núcleos estacionarios de gran superficie para aire y líquido.

rueda de recuperación rotativa

Recuperación de energía de alta eficacia para grandes caudales.

Heat Pipe Heat Exchanger

Corrientes pasivas y totalmente separadas para aplicaciones limpias.

Publicaciones relacionadas

Empieza a escribir tu término de búsqueda arriba y pulsa Intro para buscar. Pulsa Esc para cancelar.

Volver arriba
Calculadoras gratuitas de recuperación de calor y herramientas de dimensionamiento