Sistemas de recuperación de calor de flujo de refrigerante variable (VRF)

What Is VRF Heat Recovery Variable Refrigerant Flow (VRF) heat recovery systems use a single refrigerant loop with branch selector boxes to deliver simultaneous heating and cooling to different zones. Recovered heat from cooling zones is redirected to zones calling for heat, reducing the building net energy use. Heat Recovery vs Heat Pump VRF Two-pipe […]

Intercambiadores de placas brasadas frente a placas con junta

Construction Brazed plate exchangers fuse stainless plates with copper or nickel under vacuum, with no gaskets and no frame bolts. Gasketed plate exchangers clamp plates between a fixed and moving frame using elastomer gaskets, allowing plates to be added or removed. Comparison Factor Brazed Gasketed Max temperature or pressure Higher Moderate Maintenance Sealed, service-free Plates […]

Confort térmico y recuperación de calor: ASHRAE 55 e IEQ

ASHRAE 55 and Thermal Comfort ASHRAE 55 defines acceptable thermal environments through the PMV or PPD model, balancing air temperature, mean radiant temperature, humidity, air speed and clothing. Heat recovery changes supply-air conditions, so it must be designed without degrading comfort. Humidity and IEQ Enthalpy recovery transfers moisture as well as heat, helping hold indoor […]

Heat Recovery for Pools, Gyms & Arenas

Swimming pools Pool halls exhaust warm, moisture-laden air constantly. Without recovery, that latent heat is lost. An enthalpic rotary wheel or membrane plate unit recovers both temperature and humidity, slashing pool heating and dehumidification bills 40-60%. Gyms and fitness centers High occupancy means high fresh-air demand and high moisture. Sensible plate recovery handles the heating-season […]

Rueda desecante vs rueda de recuperación : cuándo usar cuál

Energy recovery wheel Transfers both sensible and (if enthalpic) latent heat between supply and exhaust air. Goal: cut HVAC heating/cooling load. Made of aluminum or polymer matrix, sometimes with a moisture-absorbing coating. Desiccant wheel Impregnated or coated with a desiccant (silica gel, molecular sieve, or zeolite). Its job is dehumidification – it pulls moisture from […]

Solución de problemas de la rueda de recuperación : fallas comunes y correcciones

Low effectiveness Cause: wheel not rotating (motor or belt failure), or condensate/fouling blocking the matrix.Fix: verify rotation and speed; wash the wheel with low-pressure water and a mild detergent; confirm belt tension. Frost or ice buildup (cold climates) Cause: exhaust-side temperature dropping below freezing.Fix: enable purge sector, reduce speed, or add preheat. See frost protection […]

Selección de intercambiador por clima : frío, templado, cálido-húmedo

Cold climates (heating-dominated) Long, sub-zero winters make frost the enemy. Rotary wheels need purge sectors and occasional defrost; plate exchangers need bypass or preheat. Frost protection strategies are mandatory. Sensible-only recovery is usually enough because winter air is dry. Temperate climates Mild seasons with both heating and cooling loads favor balanced, all-season recovery. Plate and […]