Heat Recovery Standards & Glossary

The reference sheet engineers reach for: the standards that define performance, the formulas behind every sizing, and the terms you see on a datasheet.

Standards quick-reference

StandardScopeWhat it defines
EN 308EU test method for air-to-air heat recovery devicesSensible & total heat-transfer rate and effectiveness test setup and procedure.
AHRI 1060Performance rating of air-to-air exchangers for ERV/HRV equipmentSensible, latent and enthalpy effectiveness ratings at rated conditions.
ASHRAE Std 84Method of testing air-to-air heat exchangersLaboratory procedure for sensible and total effectiveness.
EN 13141-4Residential ventilation components — performance testingField/lab test of heat-recovery ventilation units including effectiveness.
Eurovent 6/11European certification of air handling & heat-recovery unitsVoluntary performance certification and energy labelling.
EN 16798 / EPBDBuilding energy performance — ventilation requirementsIndoor environment and energy criteria that drive recovery specifications.

Formulas engineers use

Sensible effectiveness   εs = (Tsupply,out − Toutdoor) / (Tindoor − Toutdoor)
Total / enthalpy effectiveness   εt = (hsupply,out − houtdoor) / (hindoor − houtdoor)
Recovered heating power   Q = ρ · V̇ · cp · ΔT   (ρ=1.2 kg/m³, cp=1.006 kJ/kg·K)
Dew point (Magnus)   α = ln(RH/100) + 17.625·T/(243.04+T) ;   Td = 243.04·α/(17.625 − α)

Glossary

Sensible effectiveness
Fraction of the temperature difference recovered; heat only, no moisture transfer.
Total / enthalpy effectiveness
Fraction of the enthalpy (heat + moisture) difference recovered; defines ERV performance.
Rotary wheel
Revolving thermal mass that transfers heat (and moisture, if enthalpy) between streams; highest effectiveness, small carry-over.
Plate core
Fixed stack of plates. Counter-flow reaches higher effectiveness than cross-flow; streams stay fully separated.
Heat pipe
Sealed pipe with phase-change fluid; passive, no motor, compact and freeze-tolerant.
Run-around coil
Two coils linked by a circulating fluid; separates streams by distance with no air mixing.
Dew point
Temperature at which air condenses moisture; below it, surfaces wet or (if <0°C) frost.
Frost / defrost
Ice forming on the cold side in winter; managed by preheat, bypass or frost-tolerant cores.
Bypass
Damper route that lets air skip the core in mild weather or during defrost.
NTU
Number of transfer units — dimensionless size of the exchanger; higher NTU means higher effectiveness.
Face velocity
Air speed through the core face; higher speeds cut size but raise pressure drop.
Pressure drop
Fan energy needed to push air through the core; trades off against effectiveness.
ERV vs HRV
HRV = heat only; ERV = heat + moisture. ERV controls humidity load, HRV avoids moisture transfer.
Cross-contamination
Exhaust leaking into supply; eliminated by separated cores (plate, heat pipe, run-around).
Balanced flow
Equal supply and exhaust airflow; unbalanced designs recover on the lower flow.