Laundry Heat Recovery: Reusing Wash and Dryer Exhaust

Laundries are heat hogs

Commercial laundries heat vast volumes of water and run dryer exhaust hot and moist all day. Up to 70% of their energy can leave as warm water and humid air. Recovery is the fastest payback in the sector.

Two streams to catch

Hygiene and fouling

Lint and detergent demand cleanable, accessible cores. Plan a rhythm from our cleaning guide and use a hair/trap filter upstream of any water exchanger.

Retorno de inversión

High hot-water demand means recovery often pays back in 1.5-3 years, cutting water-heating energy 30-50%. Validate with a payback calculation. Leisure sites with on-site laundries (see sports facilities) benefit most.

Water side: the bigger prize

Wash water leaving at 40 to 60C carries the largest share of a laundry energy, so the water-to-water exchanger or heat pump on the drain is usually the fastest payback. A plate or coil unit pre-warms incoming cold water, directly cutting the boiler or electric load needed to reach wash temperature. Where the drain is continuous, a heat pump can lift that warmth to an even higher supply temperature.

Air side: dryer exhaust

Dryer exhaust is hot and humid, ideal for an enthalpic wheel or plate unit that returns both temperature and moisture to the make-up air, reducing the heating needed to replace it. Because dryers run in batches, the recovery should handle part-load gracefully, since a coil or wheel sized only to peak batch flow wastes effectiveness between cycles.

Keeping it clean and measurable

Lint and detergent make the air and water sides fouling-prone, so accessible, cleanable cores and an upstream strainer protect performance and hygiene. Trend the temperature recovery on both sides and the water-heating energy saved, so a falling trend flags a fouled coil before it hits the utility bill. The 30 to 50 percent water-heating saving depends on keeping both streams clean.

Preguntas frecuentes

What are the two laundry heat streams?
Wash water at 40 to 60C handled by a water-to-water exchanger or heat pump, and hot humid dryer exhaust handled by an enthalpic wheel or plate unit.

Which gives the fastest payback?
The wash-water side usually, because it is the largest energy share. A heat pump can lift it to an even higher supply temperature.

What hygiene issues matter?
Lint and detergent demand cleanable, accessible cores and an upstream strainer. Plan a cleaning rhythm.

What payback is typical?
Often 1.5 to 3 years, cutting water-heating energy by 30 to 50 percent. Validate with a payback calculation.

Preguntas frecuentes

What are the two laundry heat streams?

Wash water at 40 to 60C handled by a water-to-water exchanger or heat pump, and hot humid dryer exhaust handled by an enthalpic wheel or plate unit.

Which gives the fastest payback?

The wash-water side usually, because it is the largest energy share. A heat pump can lift it to an even higher supply temperature.

What hygiene issues matter?

Lint and detergent demand cleanable, accessible cores and an upstream strainer. Plan a cleaning rhythm.

What payback is typical?

Often 1.5 to 3 years, cutting water-heating energy by 30 to 50 percent. Validate with a payback calculation.

Especifique el intercambiador adecuado

Nuestros ingenieros dimensionan el núcleo según su caudal, temperatura y presupuesto de caída de presión, y seleccionan recuperación por placa, rotativa o caloduc según la aplicación. Lea la guía del intercambiador , o contáctenos para una especificación.

Solicitar cotización

Productos relacionados

Air-to-Air Heat Exchanger

Recuperación por placa, rotativa o caloduc para HVAC y ventilación.

Plate Heat Exchanger

Núcleos estacionarios de gran superficie para aire y líquido.

rueda de recuperación rotativa

Recuperación de energía de alta eficacia para grandes caudales.

Heat Pipe Heat Exchanger

Corrientes pasivas y totalmente separadas para aplicaciones limpias.

Publicaciones relacionadas

Empieza a escribir tu término de búsqueda arriba y pulsa Intro para buscar. Pulsa Esc para cancelar.

Volver arriba
Calculadoras gratuitas de recuperación de calor y herramientas de dimensionamiento