Specific Heat & Density of Air in Recovery Math

The two numbers you reuse constantly

  • Specific heat of air, cp: about 1.006 kJ/kg.K (or 1006 J/kg.K).
  • Density of air, rho: about 1.2 kg/m3 at 20 degC and 1 atm.

Together they give a volumetric heat capacity of roughly 1200 J/m3.K – the energy stored in each cubic metre of air per degree of temperature.

The power equation

For any recovery duty the sensible power is:

Q = rho x volumetric_flow x cp x temperature_difference

Example: 1 m3/s of air cooled by 10 K recovers about 1.2 x 1 x 1006 x 10 ≈ 12,100 W, or 12.1 kW. Multiply by operating hours and effectiveness to get daily energy, the input to any calculo de retorno de inversion.

Why constants still need care

Density falls as air heats and rises with pressure, so high-temperature or high-altitude duties shift the numbers. The epsilon-NTU method folds these into the capacity rates, but the underlying cp and rho are where every estimate starts.

Frequently asked questions

Do I use cp of dry or moist air? Use moist-air cp (~1.01) for ventilation work; the difference is small but real at high humidity.

Why is volumetric capacity useful? Because fans and ducts are sized by volume flow, not mass flow, so Q per m3/s per K is the quick design figure.

Need help specifying the right air-to-air heat recovery for your project? Contact the QIYU engineering team – WhatsApp +86 157 5335 5505, or email kuns913@gmail.com.

Preguntas frecuentes

What specific heat of air do recovery calculations use?

About 1.006 kJ per kg per K for dry air at room conditions; with moisture present you use the humid-air value, but 1.006 is the standard sensible-heat constant.

Why does air density matter in recovery?

Heat carried equals density times specific heat times flow times temperature difference; density converts volumetric flow to mass flow, and mass flow is what actually carries the energy across the core.

Preguntas frecuentes

What specific heat of air do recovery calculations use?

About 1.006 kJ per kg per K for dry air at room conditions; with moisture present you use the humid-air value, but 1.006 is the standard sensible-heat constant.

Why does air density matter in recovery?

Heat carried equals density times specific heat times flow times temperature difference; density converts volumetric flow to mass flow, and mass flow is what actually carries the energy across the core.

Especifique el intercambiador adecuado

Nuestros ingenieros dimensionan el núcleo según su caudal, temperatura y presupuesto de caída de presión, y seleccionan recuperación por placa, rotativa o caloduc según la aplicación. Lea la guía del intercambiador , o contáctenos para una especificación.

Solicitar cotización

Productos relacionados

Air-to-Air Heat Exchanger

Recuperación por placa, rotativa o caloduc para HVAC y ventilación.

Plate Heat Exchanger

Núcleos estacionarios de gran superficie para aire y líquido.

rueda de recuperación rotativa

Recuperación de energía de alta eficacia para grandes caudales.

Heat Pipe Heat Exchanger

Corrientes pasivas y totalmente separadas para aplicaciones limpias.

Publicaciones relacionadas

Empieza a escribir tu término de búsqueda arriba y pulsa Intro para buscar. Pulsa Esc para cancelar.

Volver arriba
Calculadoras gratuitas de recuperación de calor y herramientas de dimensionamiento