The epsilon-NTU Method: Predicting Heat Exchanger Performance

Effectiveness, the practical metric Effectiveness (epsilon) is the ratio of actual heat transferred to the maximum thermodynamically possible: epsilon = actual_heat_transfer / (Cmin x (Thot_in - Tcold_in)) It is the number you see quoted as "70% efficient" for a recovery core, and it is directly related to the efficiency metrics reported for air-to-air units. NTU: […]