Which Air Filter Goes Where: Application Guide by Industry and Space

Start With a Stage Strategy

Most systems run two stages: a cheap primary filter protects a finer final filter, cutting total cost. Clean spaces add a third (HEPA) stage.

Typical Arrangements by Space

Space / industry Recommended stages Notes
Offices, schools, retail G4 pre + F7 final Comfort, moderate IAQ
Commercial HVAC (better IAQ) G4 + F8/F9 Asthma/allergy, urban
Hospital wards G4 + F8 Infection control
Operating theatres / isolation G4 + F9 + H13/H14 terminal ISO 5, laminar
Pharma / aseptic G4 + F8 + H13/H14 ISO clean
Microelectronics cleanroom G4 + F9 + H14 (+ U15) Sub-micron control
Paint / spray booths G3/G4 panel + F5-F7 pocket + carbon Overspray + odour
Data centres G4 pre + F9 final Low ΔP priority
Food & beverage G4 + F7/F8 Hygiene, washable frames
Compressor / turbine intake G3/G4 + F6 pocket Equipment protection

Quick Rules of Thumb

  • Dirty, outdoor or process air first – a robust primary (G3/G4).
  • People-sensitive spaces – at least F7 and a planned HEPA for critical zones.
  • Odour or VOC complaint – add an activated-carbon stage after particulate filtration.
  • Tight energy budget – favour low initial ΔP media and keep the primary stage healthy.

Verwandte Beiträge

Beginne damit, deinen Suchbegriff oben einzugeben und drücke Enter für die Suche. Drücke ESC, um abzubrechen.