どの空気フィルターをどこへ:業界・空間別適用ガイド

Start With a Stage Strategy

Most systems run two stages: a cheap primary filter protects a finer final filter, cutting total cost. Clean spaces add a third (HEPA) stage.

Typical Arrangements by Space

Space / industry Recommended stages 注記
Offices, schools, retail G4 pre + F7 final Comfort, moderate IAQ
Commercial HVAC (better IAQ) G4 + F8/F9 Asthma/allergy, urban
Hospital wards G4 + F8 Infection control
Operating theatres / isolation G4 + F9 + H13/H14 terminal ISO 5, laminar
Pharma / aseptic G4 + F8 + H13/H14 ISO clean
Microelectronics cleanroom G4 + F9 + H14 (+ U15) Sub-micron control
Paint / spray booths G3/G4 panel + F5-F7 pocket + carbon Overspray + odour
Data centres G4 pre + F9 final Low ΔP priority
Food & beverage G4 + F7/F8 Hygiene, washable frames
Compressor / turbine intake G3/G4 + F6 pocket Equipment protection

Quick Rules of Thumb

  • Dirty, outdoor or process air first – a robust primary (G3/G4).
  • People-sensitive spaces – at least F7 and a planned HEPA for critical zones.
  • Odour or VOC complaint – add an activated-carbon stage after particulate filtration.
  • Tight energy budget – favour low initial ΔP media and keep the primary stage healthy.

A simple way to apply the stage strategy is to think of filtration as a cost cascade: spending a little more on a robust primary stage almost always reduces the lifetime cost of the final filter, because the cheap media absorbs the bulk of the coarse load. In spaces with people but no special process risk, a two-stage G4 plus F7 or F8 arrangement is usually enough, while any area handling aseptic, electronic or painted product should add the appropriate third stage. Where odour or chemical complaints appear, the answer is rarely a denser particulate filter but a dedicated activated-carbon stage placed after the particulate bank. Keeping the primary stage healthy through planned changeout is also the single most effective way to hold down fan energy, since a loaded primary drives the whole bank toward its final pressure drop.

よくある質問

Why run two filter stages instead of one?
A cheap primary filter captures the coarse dust and protects the finer, more expensive final filter, which lowers the total cost of filtration across the system.

What filter arrangement suits an operating theatre?
Typically a G4 pre-filter, an F9 final filter and an H13 or H14 terminal HEPA to reach ISO 5 with laminar flow in critical zones.

How should odour or VOC complaints be handled?
Add an activated-carbon gas-phase stage after the particulate bank, because denser dust filters do not remove smells or volatile chemicals.

Which filtration is best for a data centre?
A G4 pre-filter plus an F9 final filter is common, with low pressure drop given priority to limit fan energy in always-on facilities.

よくある質問

Why run two filter stages instead of one?

A cheap primary filter captures the coarse dust and protects the finer, more expensive final filter, which lowers the total cost of filtration across the system.

What filter arrangement suits an operating theatre?

Typically a G4 pre-filter, an F9 final filter and an H13 or H14 terminal HEPA to reach ISO 5 with laminar flow in critical zones.

How should odour or VOC complaints be handled?

Add an activated-carbon gas-phase stage after the particulate bank, because denser dust filters do not remove smells or volatile chemicals.

Which filtration is best for a data centre?

A G4 pre-filter plus an F9 final filter is common, with low pressure drop given priority to limit fan energy in always-on facilities.

適切な熱交換器を選定

当社のエンジニアが風量、温度、圧力損失の予算に合わせてコアを設計し、用途に応じて板式・回転式・ヒートパイプ回収を選定します。以下をお読みください: 熱交換器ガイド 、または仕様についてお問い合わせください。

見積りを依頼

関連製品

Air-to-Air Heat Exchanger

HVAC および換気向けの板式・回転式・ヒートパイプ回収。

Plate Heat Exchanger

空気と液体用の大表面積固定コア。

ロータリー熱回収ホイール

大風量向け高効率エネルギー回収。

Heat Pipe Heat Exchanger

清浄用途向けの受動的・完全分離流。

関連投稿

検索語を上に入力し、 Enter キーを押して検索します。キャンセルするには ESC を押してください。

トップに戻る
無料の熱回収計算ツールおよびサイジングツール