RESET Air Standard

Tabla de contenido

RESET Air is the world’s first sensor-based, performance-driven indoor-air-quality certification. Its Commercial Interiors v2.0 standard is about continuous monitoring and transparent reporting, not a one-time design check. This article summarizes the monitored parameters and the targets a space must hold.

RESET requires continuous monitors covering at least 80% of occupants across all regularly occupied space types, tracking PM2.5, TVOC, CO2, and CO. Temperature and relative humidity are monitored (no set limit) because they affect the particle and VOC sensors.

Parameter Acceptable High Performance
PM2.5 < 35 μg/m³ < 12 μg/m³
TVOC < 500 μg/m³ < 400 μg/m³
CO2 < 1,000 ppm < 600 ppm
CO < 9 ppm (combustion spaces only)

  • Data is streamed to the RESET Assessment Cloud; daily averages must stay within the Acceptable limits for three consecutive months (the data-review period) for initial certification.
  • Monitors must be RESET-accredited Grade A (calibration) or Grade B (commercial), wall-mounted in the breathing zone (0.9–1.8 m), and at least 5 m from operable windows, filters, and fresh-air diffusers.
  • Results must be shown to occupants via display, app, or QR code — transparency is part of the intent.

RESET does not mandate recovery, but good ventilation is needed to keep CO2 below 1,000 ppm in occupied spaces — and that ventilation load is exactly what an ERV offsets. Filtration (see cleanroom HVAC practice) supports the PM2.5 target. For the design-side health standard, compare with WELL v2 ventilation: RESET is monitoring-first, WELL is design-plus-performance.

Because RESET is performance-based, the recovery and filtration system must actually deliver clean air every day, not just on paper. Meter the loops and keep the commissioning records — the same discipline that ISO 50001 demands for energy.