Heat Recovery Effectiveness Test Standards

“Effectiveness” is the number every code and rating system quotes, but the value only means something if the test method is stated. This article maps the main heat recovery effectiveness test standards and how they define the metric.

Definitions

  • 顕熱効率 ηs = (Tsupply − Toutdoor) / (Textract − Toutdoor).
  • Enthalpy (total) effectiveness ηt = (hsupply − houtdoor) / (hextract − houtdoor), using moist-air enthalpy.
  • Latent effectiveness uses humidity ratio in place of enthalpy.

The Standards

Standard Scope
EN 308 Test procedures for air-to-air and flue-gas heat recovery devices (sensible and latent).
EN 13053 Rating and performance of air-handling units, including heat recovery sections and pressure drop.
EN 13141-7 Performance testing of residential mechanical supply/exhaust ventilation units.
AHRI 1060 / 1061 Energy recovery ventilators — the method ASHRAE 90.1 references for its 50% minimum.

Why the Method Matters

  • Test conditions differ: Ecodesign measures ηt at −10 °C, 0 °C, and +10 °C outdoor; ASHRAE uses design heating and cooling conditions.
  • A wheel rated 75% by AHRI 1060 may read differently under EN 308 because of how leakage and frost are handled.
  • Pressure drop is part of the story — a more effective core that needs a bigger fan can erase the saving, which is why Ecodesign SFP limits bind efficiency and fan power together.

Picking a Device Against the Numbers

Use the measured ηt from the relevant standard when checking code floors. For non-rotating critical ventilation, compare a membrane core against a wheel on the same test basis, and fold the pressure drop into the AHU selection calculation.

よくある質問

What is sensible effectiveness?
The ratio of temperature change delivered to the supply air versus the temperature difference between extract and outdoor air.

What is enthalpy effectiveness?
The same ratio using moist-air enthalpy, capturing both temperature and humidity recovery.

Which standards govern recovery testing?
EN 308, EN 13053, and EN 13141-7 in Europe, and AHRI 1060 and 1061 referenced by ASHRAE 90.1.

Why does the test method matter?
Different standards use different conditions and treat leakage and frost differently, so the same device can read differently, and pressure drop must also be considered.

よくある質問

What is sensible effectiveness?

The ratio of temperature change delivered to the supply air versus the temperature difference between extract and outdoor air.

What is enthalpy effectiveness?

The same ratio using moist-air enthalpy, capturing both temperature and humidity recovery.

Which standards govern recovery testing?

EN 308, EN 13053, and EN 13141-7 in Europe, and AHRI 1060 and 1061 referenced by ASHRAE 90.1.

Why does the test method matter?

Different standards use different conditions and treat leakage and frost differently, so the same device can read differently, and pressure drop must also be considered.

適切な熱交換器を選定

当社のエンジニアが風量、温度、圧力損失の予算に合わせてコアを設計し、用途に応じて板式・回転式・ヒートパイプ回収を選定します。以下をお読みください: 熱交換器ガイド 、または仕様についてお問い合わせください。

見積りを依頼

関連製品

Air-to-Air Heat Exchanger

HVAC および換気向けの板式・回転式・ヒートパイプ回収。

Plate Heat Exchanger

空気と液体用の大表面積固定コア。

ロータリー熱回収ホイール

大風量向け高効率エネルギー回収。

Heat Pipe Heat Exchanger

清浄用途向けの受動的・完全分離流。

関連投稿

検索語を上に入力し、 Enter キーを押して検索します。キャンセルするには ESC を押してください。

トップに戻る
無料の熱回収計算ツールおよびサイジングツール