The European Union regulates ventilation units through Regulation (EU) 1253/2014 (the “Ecodesign” Lot 21 measure). It sets binding minimum thermal efficiency and fan-power limits for units placed on the EU market, so any AHU or ERV sold in Europe must comply.
Scope
Applies to residential and non-residential ventilation units with a fan electric power of 30 W or more. Bidirectional units (supply + extract) must carry a heat recovery system (HRS) with a thermal bypass facility.
Minimum Heat Recovery Efficiency
| Unit type | Minimum thermal efficiency ηt | Bonus basis |
|---|---|---|
| Plate / thermal wheel HRS (non run-around) | 73% (from 2018) | E = (ηt − 0.73) × 3000 |
| Run-around coil HRS | 68% (from 2018) | E = (ηt − 0.68) × 3000 |
The efficiency bonus E relaxes the specific fan power limit, rewarding higher-efficiency cores. Test methods are EN 308, EN 13053 (AHUs), and EN 13141-7 (residential units). The effectiveness test standards article explains how ηt is defined.
Specific Fan Power Limits
- Non-residential unit with HRS: SFPint capped around 800–1300 W/(m³/s) depending on flow.
- Residential bidirectional unit: about 450 W/(m³/s) at reference airflow.
- All units (except dual-use) need multi-speed or variable-speed drives; a filter warning signal is required from 2018.
What Designers Must Do
Specify cores that clear 73% (or 68% for run-around) and document the product information sheet. For critical ventilation where cross-contamination is unacceptable, a membrane core is the compliant non-rotating option. These Ecodesign floors align with the EPBD zero-emission building push — efficient recovery is now table stakes in the EU market.
Labelling and Market Reality
The Ecodesign floors are not just paperwork; they reshape what can be sold. Because the efficiency bonus E relaxes the specific fan power limit, a unit with a 78% core gains compliance headroom over a bare 73% unit, which matters as fans are pushed to lower SFP. Manufacturers must publish a product information sheet documenting thermal efficiency and fan power, and that sheet is what a designer cites at spec time. For non-residential AHUs, EN 13053 governs how the recovery section is rated within the whole unit, including the pressure drop it adds. Residential bidirectional units face the same 73% logic but with a tighter SFP reference. In practice, specifying a membrane or high-efficiency plate core that clears 73% comfortably satisfies the regulation and aligns with the broader EPBD push toward zero-emission buildings, where efficient recovery is now expected rather than optional.
よくある質問
What does EU Ecodesign Regulation 1253/2014 require?
Ventilation units above 30 W fan power must carry a heat recovery system meeting minimum thermal efficiency, 73% for plate or wheel and 68% for run-around.
How does higher efficiency help compliance?
An efficiency bonus relaxes the specific fan power limit, giving design headroom as fans are pushed to lower SFP.
Which test standards apply?
EN 308, EN 13053 for air-handling units, and EN 13141-7 for residential units.
Can a membrane core comply?
Yes. A non-rotating membrane core is a compliant option where cross-contamination control is required.
よくある質問
What does EU Ecodesign Regulation 1253/2014 require?
Ventilation units above 30 W fan power must carry a heat recovery system meeting minimum thermal efficiency, 73% for plate or wheel and 68% for run-around.
How does higher efficiency help compliance?
An efficiency bonus relaxes the specific fan power limit, giving design headroom as fans are pushed to lower SFP.
Which test standards apply?
EN 308, EN 13053 for air-handling units, and EN 13141-7 for residential units.
Can a membrane core comply?
Yes. A non-rotating membrane core is a compliant option where cross-contamination control is required.
適切な熱交換器を選定
当社のエンジニアが風量、温度、圧力損失の予算に合わせてコアを設計し、用途に応じて板式・回転式・ヒートパイプ回収を選定します。以下をお読みください: 熱交換器ガイド 、または仕様についてお問い合わせください。
関連製品
HVAC および換気向けの板式・回転式・ヒートパイプ回収。
空気と液体用の大表面積固定コア。
大風量向け高効率エネルギー回収。
清浄用途向けの受動的・完全分離流。