When You Need HEPA/ULPA
Any space that must control sub-micron particles-cleanrooms, operating theatres, aseptic pharma, microelectronics, biosafety labs-uses H10-H14 (HEPA) or U15-U17 (ULPA) rated by EN 1822 MPPS efficiency.
Build Types
- Mini-pleat (separatorless) – hot-melt bead spacers, deep pleats, low ΔP; the modern standard.
- Separator (paper corrugated) – aluminium/paper separators, robust; traditional box builds.
- Box / ceiling terminals – factory-sealed flanges for cleanroom ceilings; often H13/H14.
- Gel-seal – knife-edge into a gel track for leak-free critical installs.
Typical Specifications
| Class | MPPS efficiency | Initial ΔP | Typical space |
|---|---|---|---|
| H13 | 99.95% | 120-200 Pa | OR, ISO 5, aseptic |
| H14 | 99.995% | 150-250 Pa | ISO 5 critical |
| U15 | 99.9995% (≥0.12 µm) | 200-300 Pa | ULPA ISO 3-4 |
Selection Checklist
- Match class to the cleanroom ISO grade (H13/H14 for ISO 5; U15+ for tighter).
- Specify leakage test (scan) and a frame/seal method (gel, knife, gasket).
- Confirm max temperature and humidity limits of the media.
- Plan PAO/DOP integrity testing at install and annually.
.yc-spec-wrap{margin:36px 0 28px}
.yc-spec-wrap figure{margin:0 0 24px;text-align:center}
.yc-spec-wrap figure img{max-width:100%;height:auto;border:1px solid #e5e7eb;border-radius:8px}
.yc-spec-wrap figcaption{font-size:14px;color:#6b7280;margin-top:8px}
.yc-spec{width:100%;border-collapse:collapse;font-size:15px;margin:8px 0 16px}
.yc-spec th,.yc-spec td{border:1px solid #d1d5db;padding:9px 12px;text-align:left;vertical-align:top}
.yc-spec th{background:#1f3a5f;color:#fff}
.yc-spec tr:nth-child(even) td{background:#f8fafc}
.yc-note{font-size:14px;color:#6b7280;margin-top:4px}
.yc-thumb-row{display:flex;gap:16px;flex-wrap:wrap;margin:0 0 20px}
.yc-thumb-row figure{flex:1 1 240px;margin:0;text-align:center}
Model Range & Specifications

| モデル | EN 1822 class | MPPS efficiency | Construction | Typical initial ΔP | Final ΔP (replace) |
|---|---|---|---|---|---|
| 26YC-HP-H11 | H11 | ≥ 95% | Minipleat, aluminium frame, 78–292 mm | 100–140 Pa | 450–600 Pa |
| 26YC-HP-H12 | H12 | ≥ 99.5% | Minipleat, aluminium frame, 150–292 mm | 140–180 Pa | |
| 26YC-HP-H13 | H13 | ≥ 99.95% | Minipleat, aluminium frame, 220–292 mm | 200–250 Pa | |
| 26YC-HP-H14 | H14 | ≥ 99.995% | Minipleat, aluminium frame, 292 mm | 230–280 Pa | |
| 26YC-UL-U15 | U15 | ≥ 99.9995% | ULPA minipleat, aluminium frame, 292 mm | 250–300 Pa |
Standard face sizes 610 × 610 mm and 610 × 762 mm, rated 1 000–1 700 m³/h; aluminium-separator versions for high-temperature duty (up to 250 °C with special sealant and frame); every filter individually scanned and tested to EN 1822 with certificate supplied. PU or silicone gaskets, custom sizes on request.
よくある質問
What defines HEPA filter efficiency?
Efficiency is rated at the most penetrating particle size, about 0.1 to 0.3 micrometres; H13 is 99.95 percent and H14 is 99.995 percent.
What is the difference between mini-pleat and separator HEPA?
Mini-pleat uses hot-melt separators for a deeper pack and lower pressure drop, while separator types use corrugated foil and are very robust.
When is ULPA filtration required?
ULPA is used in ISO class 3 to 4 cleanrooms where control of particles at or below 0.12 micrometres is needed.
Must HEPA filters be leak tested?
Yes, a PAO or DOP scan after installation confirms media and seal integrity before the space is certified.
よくある質問
What defines HEPA filter efficiency?
Efficiency is rated at the most penetrating particle size, about 0.1 to 0.3 micrometres; H13 is 99.95 percent and H14 is 99.995 percent.
What is the difference between mini-pleat and separator HEPA?
Mini-pleat uses hot-melt separators for a deeper pack and lower pressure drop, while separator types use corrugated foil and are very robust.
When is ULPA filtration required?
ULPA is used in ISO class 3 to 4 cleanrooms where control of particles at or below 0.12 micrometres is needed.
Must HEPA filters be leak tested?
Yes, a PAO or DOP scan after installation confirms media and seal integrity before the space is certified.
適切な熱交換器を選定
当社のエンジニアが風量、温度、圧力損失の予算に合わせてコアを設計し、用途に応じて板式・回転式・ヒートパイプ回収を選定します。以下をお読みください: 熱交換器ガイド 、または仕様についてお問い合わせください。
関連製品
HVAC および換気向けの板式・回転式・ヒートパイプ回収。
空気と液体用の大表面積固定コア。
大風量向け高効率エネルギー回収。
清浄用途向けの受動的・完全分離流。