Building Performance Standards Carbon

目次

Building Performance Standards (BPS) are laws that cap a building’s greenhouse-gas emissions and tighten the cap over time, with penalties for exceeding it. The flagship is New York City’s Local Law 97 (LL97) of 2019; this article summarizes how it works and the role of heat recovery in compliance.

LL97 covers most buildings over 25,000 ft² (or groups on one tax lot over 50,000 ft²). Emissions limits are set per occupancy class in kg CO2e per ft² per year, with a stricter second period:

Occupancy 2024–2029 cap 2030–2034 cap
Business (B) 0.00846 0.00453
Multifamily (R-2) 0.00675 0.00407
Mercantile (M) 0.01181 0.00403
Assembly (A) 0.01079 0.00420
Storage (S) 0.00403 0.00110

The penalty for exceeding the cap is $268 per metric ton CO2e per year, with no cap on the fine. Citywide goals are 40% below 2005 by 2030 and 80% by 2050.

  • Washington DC BEPS — building performance standards with compliance deadlines by type.
  • Boston BERDO 2.0 — emissions caps with a 2050 net-zero target and a carbon-credit trading option.
  • Denver and several states have adopted or proposed BPS frameworks.
  • EU — the EPBD drives the supply side via ZEB; national renovation mandates add performance floors.

Ventilation and heating dominate most building emissions. Cutting the ventilation load with a membrane ERV or wheel, then electrifying the remainder with heat pumps, is a primary LL97 compliance lever — directly supporting the decarbonization sequence. Track savings with the metering discipline in carbon accounting for HVAC so the emissions math holds up to audit.