Air-to-Air Heat Exchanger

An air-to-air heat exchanger transfers heat between two separate air streams without mixing them. It is the core component of HRV and ERV systems, letting you cut heating and cooling load while keeping supply air volumes intact.

How an air-to-air heat exchanger works

Warm, stale exhaust passes one side of the core while cooler fresh supply passes the other. Through a stationary plate, a rotating wheel, or sealed heat pipes, energy crosses the divider. Sensible units move temperature only; enthalpy (total-energy) units also transfer moisture via a permeable or desiccant surface.

Main configurations

  • Fixed plate – stationary, no moving parts, easiest to clean.
  • Rotary wheel – higher effectiveness, carries a small carryover stream.
  • Heat pipe – passive, separates the two airstreams by distance.
  • Run-around coil – for streams that cannot share a core.

Key specifications

Parameter Typical range
Effectiveness (sensible) 50–85%
Face velocity 1.5–3.5 m/s
Pressure drop 80–300 Pa
Materials Aluminum, 304/316L, coated
Temperature range -40 to 200 °C

Typical applications

Commercial HVAC, data-center make-up air, cleanrooms, paint booths, drying and industrial ventilation. See counter-flow air-to-air applications.

Read the full heat exchanger guide, or compare the plate heat exchanger and rotary heat wheel.

Need a specification? 견적 요청 or download our selection checklist. Our engineers size the core to your airflow, temperature and pressure-drop budget.

위에 검색어를 입력하고 Enter 키를 눌러 검색하세요. 취소하려면 ESC 키를 누르세요.

맨 위로
Free heat-recovery calculators & sizing tools