制药与洁净室排气热回收

P制药工厂与洁净室会输送大量经 HEPA 过滤的空气。相关规范通常禁止以下行为: 再循环 可能携带污染物的排风,但其中的能量仍可通过物理隔离的换热器回收。

Why Separation Is Mandatory

  • GMP 与 HVAC 规范要求将隔离区的排风排出而非再利用。
  • 交叉污染可能危及产品质量。
  • 分离式芯体只传递热量,绝不传递空气或颗粒。

Recommended Technologies

技术 适用于制药/洁净室
板式(逆流) Excellent – zero carryover, washable
热管 Excellent – no moving parts, isolated streams
间接式循环盘管 排风远离送风时适用
Rotary wheel Avoid – carryover risk despite purge

Integration Points

  • 从一般 AHU 排风(而非隔离区排风)回收热量。
  • 对更衣及辅助区域的新风进行预热或预冷。
  • 在存在清洗剂的场所,使用不锈钢或带涂层的芯体。
  • 在调试前与合格人员(QP)一同验证。

In pharma and cleanroom duty, recovery must respect the air-handling hierarchy. Recover only from general or support-zone exhaust, never from containment or hazardous streams, and keep the recovery core outside the classified envelope so classifications are unchanged. Preserve the pressure cascade: the make-up air pre-conditioned by recovery still passes through the normal HEPA and control sequence. Specify hygienic materials and cleanable cores where cleaning agents or sporicides are present, and document the design for validation. Involve the qualified person before commissioning so the recovery is accepted as part of the qualified system. Our plate and heat-pipe cores keep streams fully separated for this duty.

常见问题

能否从隔离操作亭回收热量?
仅可通过一般排风上的分离芯体回收显热;受污染的流体本身保持单向。

热回收是否影响洁净度分级?
不会,只要回收芯体位于洁净区之外,且按设计保持流体分离即可。

常见问题

能否从隔离操作亭回收热量?

仅可通过一般排风上的分离芯体回收显热;受污染的流体本身保持单向。

热回收是否影响洁净度分级?

不会,只要回收芯体位于洁净区之外,且按设计保持流体分离即可。

选型合适的换热器

我们的工程师会根据您的风量、温度和压降预算设计芯体,并按应用选择板式、旋转式或热管回收。阅读 换热器指南 ,或联系我们获取规格书。