AHRI 1060: Rating Air-to-Air Energy Recovery Ventilation Equipment

What AHRI 1060 Covers AHRI 1060 is the Air-Conditioning, Heating, and Refrigeration Institute standard that rates air-to-air energy recovery ventilation (ERV) and heat recovery ventilation (HRV) equipment. It defines how manufacturers must test and report the performance that buyers actually compare: sensible effectiveness, total (enthalpy) effectiveness, rated airflow, external static pressure, and supply- and exhaust-side […]

EN 308: Air-to-Air Heat-Transfer Test Methods

Purpose of EN 308 EN 308 is the European standard that specifies test procedures for air-to-air heat transfer in heat recovery equipment. Rather than setting a pass/fail threshold, it defines how to measure temperature effectiveness and, for enthalpy devices, moisture effectiveness under controlled inlet conditions. What Gets Measured The test fixes inlet dry-bulb temperatures and, […]

The epsilon-NTU Method: Predicting Heat Exchanger Performance

Effectiveness, the practical metric Effectiveness (epsilon) is the ratio of actual heat transferred to the maximum thermodynamically possible: epsilon = actual_heat_transfer / (Cmin x (Thot_in – Tcold_in)) It is the number you see quoted as “70% efficient” for a recovery core, and it is directly related to the efficiency metrics reported for air-to-air units. NTU: […]

Dew-Point vs Temperature Effectiveness in ERV

Temperature effectiveness (sensible) Temperature effectiveness compares supply temperature change to the maximum possible: epsilon_T = (T_supply_out – T_supply_in) / (T_exhaust_in – T_supply_in) This is the number a sensible plate reports, and it is what most generic “efficiency” labels mean. Dew-point effectiveness (total / enthalpy) For an enthalpy wheel or membrane, moisture matters, so effectiveness is […]

Métriques d'efficacité de récupération expliquées

When comparing heat recovery products, efficiency numbers can be confusing. Manufacturers may quote temperature effectiveness, sensible recovery efficiency, or total energy recovery. Understanding these metrics helps you make fair comparisons and avoid under- or over-sizing equipment. Temperature Effectiveness (Sensible) Sensible effectiveness is the most common metric for air-to-air heat exchangers. It compares the actual temperature […]