A heat exchanger only saves energy if the recovered heat exceeds the extra electricity needed to push air through it. That trade-off is governed by 圧力損失.

What Drives Pressure Drop?

  • Face velocity (higher speed = steeper rise)
  • Core depth and plate count
  • Surface corrugation and coating thickness
  • Dust or fiber loading on fins

Reading a Performance Curve

Manufacturers publish pressure drop vs airflow. A good design operates on the flatter part of the curve — typically 2–3 m/s face velocity for plates. Beyond that, fan power rises faster than recovered heat.

Calculating Net Savings

Net savings = recovered thermal energy − extra fan energy. As a rule of thumb, keep added pressure drop under 100–150 Pa for ventilation applications unless efficiency gains are large.

Design Tips

  • Use EC plug fans to capture part-load efficiency.
  • Add pre-filters to keep the core clean.
  • Provide access for periodic cleaning.
  • Model the full year, not just design day.

Put pressure drop next to recovered energy early in the selection, not after. Apply the fan affinity laws when forecasting part-load savings: halving flow roughly quarters the fan power, so variable-speed control pays back fast on duty with wide load swings. Track specific fan power, the watts per cubic meter per second of air moved, as a single figure of merit across competing cores. Use the published performance curve rather than a single point, and model the annual load profile so the design sits on the efficient part of the curve for most hours. Pre-filtration and a cleaning plan protect that position over time. Our performance methodology explains how effectiveness and pressure drop trade off in practice.

よくある質問

Is a bigger core always better?
Not always. A deeper core raises efficiency but also pressure drop; optimize the combination.

How often should I clean?
Inspect quarterly in dusty duty; clean when pressure drop rises 15–20 % above baseline.

よくある質問

Is a bigger core always better?

Not always. A deeper core raises efficiency but also pressure drop; optimize the combination.

How often should I clean?

Inspect quarterly in dusty duty; clean when pressure drop rises 15–20 % above baseline.

適切な熱交換器を選定

当社のエンジニアが風量、温度、圧力損失の予算に合わせてコアを設計し、用途に応じて板式・回転式・ヒートパイプ回収を選定します。以下をお読みください: 熱交換器ガイド 、または仕様についてお問い合わせください。

見積りを依頼

関連製品

Air-to-Air Heat Exchanger

HVAC および換気向けの板式・回転式・ヒートパイプ回収。

Plate Heat Exchanger

空気と液体用の大表面積固定コア。

ロータリー熱回収ホイール

大風量向け高効率エネルギー回収。

Heat Pipe Heat Exchanger

清浄用途向けの受動的・完全分離流。

関連投稿

検索語を上に入力し、 Enter キーを押して検索します。キャンセルするには ESC を押してください。

トップに戻る
無料の熱回収計算ツールおよびサイジングツール