A 只有当回收的热量超过推动空气通过该换热器所需的额外电力时,换热器才节能。这一权衡由以下因素决定: 压降.
What Drives Pressure Drop?
- 迎面风速(速度越高,上升越陡)
- 芯体深度与板片数量
- 表面波纹与涂层厚度
- 翅片上的粉尘或纤维附着
Reading a Performance Curve
厂家会公布压降与风量的关系。良好的设计工作在曲线较平缓的部分——板翅通常迎面风速为2~3 m/s。超出这一范围,风机功率的上升会快于回收的热量。
Calculating Net Savings
净节约 = 回收的热能 − 风机额外能耗。经验法则:除非效率收益很大,否则通风应用应将附加压降保持在100~150 Pa以下。
Design Tips
- 使用EC插件式风机以捕获部分负荷效率。
- 增设预过滤器以保持芯体清洁。
- 提供定期清洗的检修通道。
- 要模拟全年,而不仅是设计日。
Put pressure drop next to recovered energy early in the selection, not after. Apply the fan affinity laws when forecasting part-load savings: halving flow roughly quarters the fan power, so variable-speed control pays back fast on duty with wide load swings. Track specific fan power, the watts per cubic meter per second of air moved, as a single figure of merit across competing cores. Use the published performance curve rather than a single point, and model the annual load profile so the design sits on the efficient part of the curve for most hours. Pre-filtration and a cleaning plan protect that position over time. Our performance methodology explains how effectiveness and pressure drop trade off in practice.
常见问题
更大的芯体总是更好吗?
不一定。更深的芯体提高效率,但也增加压降;需优化组合。
我应该多久清洗一次?
在多粉尘工况下每季度检查;当压降比基线升高15~20%时进行清洗。
常见问题
更大的芯体总是更好吗?
不一定。更深的芯体提高效率,但也增加压降;需优化组合。
我应该多久清洗一次?
在多粉尘工况下每季度检查;当压降比基线升高15~20%时进行清洗。
相关产品
面向暖通空调与通风的板式、旋转式或热管回收。
空气与液体用大表面积固定芯体。
大风量用高效能量回收。
用于洁净场合的被动、完全分离气流。