CHP Case Study: Cogeneration in a Real-World Facility

The site

A 12,000 m2 district with a hospital wing, pool, and offices had a steady year-round heat demand and paid high grid electricity prices. A 500 kWe natural-gas CHP engine was installed to supply base-load power and capture jacket plus exhaust heat for space heating and domestic hot water.

What it recovered

  • Electrical output: 500 kWe continuous.
  • Recovered heat: approx 650 kWth at 80-90C water.
  • Total fuel efficiency: ~85% vs ~40% for grid power alone.

Where HVAC recovery helped

The CHP covered the high-grade water loop, but the buildings still vented conditioned air. Adding plate air-to-air exchangers on the ventilation side captured the remaining low-grade exhaust, complementing the water loop described in our CHP overview.

Results

  • Site CO2 cut by ~28%.
  • Energy cost reduced by ~22%.
  • Simple payback: 4.5 years.

Lessons

CHP pays only when heat demand is continuous and matches engine output – oversizing wastes the advantage. Validate with a payback calculation and see waste-heat recovery basics for the full heat ladder.

Operating the combined system

In practice the CHP engine and the plate air-to-air exchangers operate on different loops but share a goal: extract value from every grade of heat. The CHP satisfies the steady high-grade demand for space heating and hot water, while the ventilation-side plates trim the low-grade exhaust losses that the engine cannot reach. Coordinating their control avoids the CHP exporting heat the building cannot use at that moment.

Lessons on matching output

The case reinforces a core CHP rule: the engine must be sized to the continuous heat demand, not the peak. An oversized unit spends part of the year dumping heat or throttling, erasing the efficiency gain. The 4.5-year payback assumed a well-matched load profile and steady operation, which is why a payback calculation belongs in the feasibility stage, not after installation.

Measuring the result

The reported 22 percent energy-cost and 28 percent CO2 reductions came from comparing metered site performance against the pre-CHP baseline, including the ventilation recovery contribution. Tracking both the water-loop and air-side savings separately keeps the business case transparent and shows where further trimming, better control or wider recovery coverage, is still possible.

よくある質問

What did the CHP case study recover?
A 500 kWe engine plus about 650 kWth at 80 to 90C water, lifting total fuel efficiency to about 85 percent versus roughly 40 percent for grid power alone.

How did HVAC recovery help the CHP site?
Plate air-to-air exchangers captured the low-grade ventilation exhaust that the water loop could not reach, complementing the CHP.

What were the reported results?
Site CO2 fell about 28 percent, energy cost about 22 percent, with a simple payback of 4.5 years.

What is the key CHP lesson?
Size the engine to the continuous, matched heat demand. Oversizing that dumps heat wastes the advantage. Validate with a payback calculation.

よくある質問

What did the CHP case study recover?

A 500 kWe engine plus about 650 kWth at 80 to 90C water, lifting total fuel efficiency to about 85 percent versus roughly 40 percent for grid power alone.

How did HVAC recovery help the CHP site?

Plate air-to-air exchangers captured the low-grade ventilation exhaust that the water loop could not reach, complementing the CHP.

What were the reported results?

Site CO2 fell about 28 percent, energy cost about 22 percent, with a simple payback of 4.5 years.

What is the key CHP lesson?

Size the engine to the continuous, matched heat demand. Oversizing that dumps heat wastes the advantage. Validate with a payback calculation.

適切な熱交換器を選定

当社のエンジニアが風量、温度、圧力損失の予算に合わせてコアを設計し、用途に応じて板式・回転式・ヒートパイプ回収を選定します。以下をお読みください: 熱交換器ガイド 、または仕様についてお問い合わせください。

見積りを依頼

関連製品

Air-to-Air Heat Exchanger

HVAC および換気向けの板式・回転式・ヒートパイプ回収。

Plate Heat Exchanger

空気と液体用の大表面積固定コア。

ロータリー熱回収ホイール

大風量向け高効率エネルギー回収。

Heat Pipe Heat Exchanger

清浄用途向けの受動的・完全分離流。

関連投稿

検索語を上に入力し、 Enter キーを押して検索します。キャンセルするには ESC を押してください。

トップに戻る
無料の熱回収計算ツールおよびサイジングツール