Unidades manejadoras de aire (AHU) e integración de recuperación de calor

An air handling unit (AHU) conditions outdoor air before it enters a building. Without recovery, that outdoor air must be heated or cooled from scratch every hour. Adding a heat recovery core to the AHU is the single highest-impact energy measure for ventilation systems.

Where the Exchanger Sits in an AHU

The recovery core is placed in the exhaust-to-supply air path, usually after the filters and before the supply fan. In modular AHUs, it drops into a dedicated section sized for the core dimensions.

Matching Exchanger Type to AHU Duty

AHU duty Recommended core
General office fresh air Counter-flow plate or enthalpy wheel
Laboratory / hospital (clean) Plate (no carryover)
High humidity climate Rueda rotativa de entalpía
Retrofit, limited space Heat pipe or run-around coil

Integration Tips

  • Keep face velocity in the 2–3 m/s range for balanced efficiency and pressure drop.
  • Add bypass dampers for free cooling in mild weather.
  • Use EC fans to capture part-load savings.
  • Specify easy-access doors for core cleaning.

Vea nuestra modular AHU solutions for recovery-ready configurations.

Factory assembly and casing quality matter as much as the core itself. Specify a casing leakage class per EN 1886 so recovered air is not lost to the mechanical room, and confirm the core section has tool-free access doors for service. Place the filter stages ahead of the recovery core to protect it, and keep the supply fan after the core to avoid pressurizing the exhaust side. For clean applications, verify that face velocity and core bypass meet the required air-change rates. Commission the unit with the building management system so the bypass opens on cool days and the recovery core carries the heating or cooling load the rest of the year. Explore modular AHU solutions with recovery-ready sections in standard sizes.

Preguntas frecuentes

Can I retrofit an existing AHU?
Yes, if there is physical space and a matching exhaust duct. Heat pipes and run-around coils are the most retrofit-friendly.

Does recovery hurt IAQ?
No. Plate and heat-pipe cores keep streams separate; only enthalpy wheels transfer a little moisture, which is managed by purge sectors.

Preguntas frecuentes

Can I retrofit an existing AHU?

Yes, if there is physical space and a matching exhaust duct. Heat pipes and run-around coils are the most retrofit-friendly.

Does recovery hurt IAQ?

No. Plate and heat-pipe cores keep streams separate; only enthalpy wheels transfer a little moisture, which is managed by purge sectors.

Especifique el intercambiador adecuado

Nuestros ingenieros dimensionan el núcleo según su caudal, temperatura y presupuesto de caída de presión, y seleccionan recuperación por placa, rotativa o caloduc según la aplicación. Lea la guía del intercambiador , o contáctenos para una especificación.

Solicitar cotización

Productos relacionados

Air-to-Air Heat Exchanger

Recuperación por placa, rotativa o caloduc para HVAC y ventilación.

Plate Heat Exchanger

Núcleos estacionarios de gran superficie para aire y líquido.

rueda de recuperación rotativa

Recuperación de energía de alta eficacia para grandes caudales.

Heat Pipe Heat Exchanger

Corrientes pasivas y totalmente separadas para aplicaciones limpias.

Publicaciones relacionadas

Empieza a escribir tu término de búsqueda arriba y pulsa Intro para buscar. Pulsa Esc para cancelar.

Volver arriba
Calculadoras gratuitas de recuperación de calor y herramientas de dimensionamiento