Unités de traitement d'air (AHU) et intégration de récupération de chaleur

An air handling unit (AHU) conditions outdoor air before it enters a building. Without recovery, that outdoor air must be heated or cooled from scratch every hour. Adding a heat recovery core to the AHU is the single highest-impact energy measure for ventilation systems.

Where the Exchanger Sits in an AHU

The recovery core is placed in the exhaust-to-supply air path, usually after the filters and before the supply fan. In modular AHUs, it drops into a dedicated section sized for the core dimensions.

Matching Exchanger Type to AHU Duty

AHU duty Recommended core
General office fresh air Counter-flow plate or enthalpy wheel
Laboratory / hospital (clean) Plate (no carryover)
High humidity climate Roue rotative d'enthalpie
Retrofit, limited space Heat pipe or run-around coil

Integration Tips

  • Keep face velocity in the 2–3 m/s range for balanced efficiency and pressure drop.
  • Add bypass dampers for free cooling in mild weather.
  • Use EC fans to capture part-load savings.
  • Specify easy-access doors for core cleaning.

Voir notre modular AHU solutions for recovery-ready configurations.

Factory assembly and casing quality matter as much as the core itself. Specify a casing leakage class per EN 1886 so recovered air is not lost to the mechanical room, and confirm the core section has tool-free access doors for service. Place the filter stages ahead of the recovery core to protect it, and keep the supply fan after the core to avoid pressurizing the exhaust side. For clean applications, verify that face velocity and core bypass meet the required air-change rates. Commission the unit with the building management system so the bypass opens on cool days and the recovery core carries the heating or cooling load the rest of the year. Explore modular AHU solutions with recovery-ready sections in standard sizes.

Questions fréquemment posées

Can I retrofit an existing AHU?
Yes, if there is physical space and a matching exhaust duct. Heat pipes and run-around coils are the most retrofit-friendly.

Does recovery hurt IAQ?
No. Plate and heat-pipe cores keep streams separate; only enthalpy wheels transfer a little moisture, which is managed by purge sectors.

Questions fréquemment posées

Can I retrofit an existing AHU?

Yes, if there is physical space and a matching exhaust duct. Heat pipes and run-around coils are the most retrofit-friendly.

Does recovery hurt IAQ?

No. Plate and heat-pipe cores keep streams separate; only enthalpy wheels transfer a little moisture, which is managed by purge sectors.

Spécifiez le bon échangeur

Nos ingénieurs dimensionnent le noyau selon votre débit, température et budget de perte de charge, et choisissent la récupération par plaque, rotative ou caloduc selon l'application. Lisez le guide de l'échangeur , ou contactez-nous pour une spécification.

Demander un devis

Produits connexes

Air-to-Air Heat Exchanger

Récupération par plaque, rotative ou caloduc pour le CVC et la ventilation.

Plate Heat Exchanger

Noyaux stationnaires à grande surface pour l'air et le liquide.

roue de récupération rotative

Récupération d'énergie à haute efficacité pour grands débits.

Heat Pipe Heat Exchanger

Courants passifs et totalement séparés pour applications propres.

Articles similaires

Commencez à saisir votre recherche ci-dessus et pressez Entrée pour rechercher. ESC pour annuler.

Retour en haut
Calculateurs gratuits de récupération de chaleur et outils de dimensionnement