An air handling unit (AHU) 在建筑进风前处理室外空气。若无回热,该室外空气每小时都要从零开始加热或冷却。为AHU增加热回收芯体是通风系统单项影响最大的节能措施。
Where the Exchanger Sits in an AHU
回热芯体置于排风至送风的路径中,通常在过滤器之后、送风机之前。在模块化AHU中,它落入按芯体尺寸设计的专用段。
Matching Exchanger Type to AHU Duty
| AHU用途 | 推荐芯体 |
|---|---|
| 普通办公室新风 | 逆流板翅或焓轮 |
| 实验室/医院(洁净) | 板翅(无携带) |
| 高湿度气候 | 旋转式全热轮 |
| 改造、空间有限 | 热管或环路热回收盘管 |
Integration Tips
- 将迎面风速保持在2~3 m/s范围内,以平衡效率与压降。
- 在温和天气下为自然冷却增设旁通风阀。
- 使用EC风机以捕获部分负荷下的节能收益。
- 指定便于检修的门,以便清洗芯体。
查看我们的 模块化AHU解决方案 用于回热就绪的配置。
Factory assembly and casing quality matter as much as the core itself. Specify a casing leakage class per EN 1886 so recovered air is not lost to the mechanical room, and confirm the core section has tool-free access doors for service. Place the filter stages ahead of the recovery core to protect it, and keep the supply fan after the core to avoid pressurizing the exhaust side. For clean applications, verify that face velocity and core bypass meet the required air-change rates. Commission the unit with the building management system so the bypass opens on cool days and the recovery core carries the heating or cooling load the rest of the year. Explore 模块化AHU解决方案 with recovery-ready sections in standard sizes.
常见问题
我可以对现有AHU进行改造吗?
可以,只要有物理空间且排风管道匹配。热管和环路盘管最易于改造。
回热会损害IAQ(室内空气质量)吗?
不会。板翅和热管芯体保持气流隔离;只有焓轮会传递少量湿气,而这由吹扫扇区管理。
常见问题
我可以对现有AHU进行改造吗?
可以,只要有物理空间且排风管道匹配。热管和环路盘管最易于改造。
回热会损害IAQ(室内空气质量)吗?
不会。板翅和热管芯体保持气流隔离;只有焓轮会传递少量湿气,而这由吹扫扇区管理。
相关产品
面向暖通空调与通风的板式、旋转式或热管回收。
空气与液体用大表面积固定芯体。
大风量用高效能量回收。
用于洁净场合的被动、完全分离气流。