Heat Recovery Effectiveness Test Standards

“Effectiveness” is the number every code and rating system quotes, but the value only means something if the test method is stated. This article maps the main heat recovery effectiveness test standards and how they define the metric.

Definitions

  • 현열 효율 ηs = (Tsupply − Toutdoor) / (Textract − Toutdoor).
  • Enthalpy (total) effectiveness ηt = (hsupply − houtdoor) / (hextract − houtdoor), using moist-air enthalpy.
  • Latent effectiveness uses humidity ratio in place of enthalpy.

The Standards

Standard Scope
EN 308 Test procedures for air-to-air and flue-gas heat recovery devices (sensible and latent).
EN 13053 Rating and performance of air-handling units, including heat recovery sections and pressure drop.
EN 13141-7 Performance testing of residential mechanical supply/exhaust ventilation units.
AHRI 1060 / 1061 Energy recovery ventilators — the method ASHRAE 90.1 references for its 50% minimum.

Why the Method Matters

  • Test conditions differ: Ecodesign measures ηt at −10 °C, 0 °C, and +10 °C outdoor; ASHRAE uses design heating and cooling conditions.
  • A wheel rated 75% by AHRI 1060 may read differently under EN 308 because of how leakage and frost are handled.
  • Pressure drop is part of the story — a more effective core that needs a bigger fan can erase the saving, which is why Ecodesign SFP limits bind efficiency and fan power together.

Picking a Device Against the Numbers

Use the measured ηt from the relevant standard when checking code floors. For non-rotating critical ventilation, compare a membrane core against a wheel on the same test basis, and fold the pressure drop into the AHU selection calculation.

자주 묻는 질문

What is sensible effectiveness?
The ratio of temperature change delivered to the supply air versus the temperature difference between extract and outdoor air.

What is enthalpy effectiveness?
The same ratio using moist-air enthalpy, capturing both temperature and humidity recovery.

Which standards govern recovery testing?
EN 308, EN 13053, and EN 13141-7 in Europe, and AHRI 1060 and 1061 referenced by ASHRAE 90.1.

Why does the test method matter?
Different standards use different conditions and treat leakage and frost differently, so the same device can read differently, and pressure drop must also be considered.

자주 묻는 질문

What is sensible effectiveness?

The ratio of temperature change delivered to the supply air versus the temperature difference between extract and outdoor air.

What is enthalpy effectiveness?

The same ratio using moist-air enthalpy, capturing both temperature and humidity recovery.

Which standards govern recovery testing?

EN 308, EN 13053, and EN 13141-7 in Europe, and AHRI 1060 and 1061 referenced by ASHRAE 90.1.

Why does the test method matter?

Different standards use different conditions and treat leakage and frost differently, so the same device can read differently, and pressure drop must also be considered.

적합한 열교환기 선정

당사 엔지니어가 풍량, 온도, 압력 손실 예산에 맞춰 코어를 설계하고, 적용에 따라 판형·회전식·히트파이프 회수를 선택합니다. 다음을 읽으세요: 열교환기 가이드 , 또는 사양 관련 문의를 주세요.

견적 요청

관련 제품

Air-to-Air Heat Exchanger

HVAC 및 환기용 판형·회전식·히트파이프 회수.

Plate Heat Exchanger

공기 및 액체용 대면적 고정 코어.

회전식 열회수 휠

대풍량용 고효율 에너지 회수.

Heat Pipe Heat Exchanger

청정 적용을 위한 수동적·완전 분리 유동.

관련 게시물

위에 검색어를 입력하고 Enter 키를 눌러 검색하세요. 취소하려면 ESC 키를 누르세요.

맨 위로
무료 열회수 계산기 및 사이징 도구