AHU Heat Recovery Selection Calculation: A Step-by-Step Method

Step 1 – Known airflow

Start with the supply/exhaust airflow Q (m3/h). For balanced AHUs, Q_supply approx Q_exhaust.

Step 2 – Temperature difference

Find the outdoor design temperature T_out and the exhaust (room return) temperature T_exp. The available temperature lift is DeltaT = T_exp – T_out.

Step 3 – Effectiveness

Choose an effectiveness epsilon (typical plate 0.60-0.75, rotary 0.75-0.85). Recovered temperature into supply air: T_rec = epsilon x DeltaT.

Step 4 – Heat recovered

Q_rec [W] = rho x c_p x Q x T_rec, where rho=1.2 kg/m3 and c_p=1005 J/(kg.K). Convert Q from m3/h to m3/s (divide by 3600).

Step 5 – Pressure drop & fan cost

Every Pascal of recovery-device pressure drop raises fan power: P_fan [W] = Q[Pa] x Q[m3/s] / eta_fan. Balance effectiveness against fan energy using our pressure-drop guide.

Step 6 – Payback

Annual energy saved = Q_rec x operating hours x (1 – penalty) x energy price. Compare against first cost and the payback method. Pick the device type from selection by application.

Worked example

Q=10000 m3/h, T_out=-10C, T_exp=22C, epsilon=0.70 -> T_rec=22.4C, Q_rec approx 75 kW. At 4000 h/yr and 0.10 EUR/kWh that is about 30,000 EUR/yr saved.

Effectiveness versus pressure drop

The calculation above maximizes recovered heat, but a higher-effectiveness core usually costs more pressure drop, and that pressure drop is paid continuously by the fan. The true optimum is not the highest epsilon but the point where the value of extra recovered heat equals the extra fan energy it demands. Run the fan-power term in Step 5 for two or three candidate cores before choosing.

Part-load and real operation

Design-day calculations flatter a device; most hours are at part load. Check how effectiveness and pressure drop behave as airflow falls, and whether the control modulates the core or simply bypasses it. A unit that performs well only at full flow may under-deliver across the annual load profile, hurting the payback estimate.

Verifying the installed result

After commissioning, measure the actual supply-temperature rise and pressure drop and compare them to the calculation. Differences reveal fouling, bypass leakage, or a mismatch between assumed and real airflow. Re-running the steps with measured values closes the loop between design intent and delivered performance, and supports any performance guarantee.

자주 묻는 질문

How do I calculate heat recovered in an AHU?
Use Q_rec equals rho times c_p times airflow times effectiveness times the temperature difference, with rho 1.2 and c_p 1005, converting cubic metres per hour to cubic metres per second.

Should I maximize effectiveness?
Not always. Higher effectiveness often means more pressure drop and fan energy, so optimize the trade-off rather than chase the highest number.

What fan-power formula applies?
Fan power equals pressure drop times airflow divided by fan efficiency. Balance this against the heat recovered when choosing a core.

How do I verify installed performance?
Measure the actual supply temperature rise and pressure drop and compare them to the calculation. Trend for fouling or bypass leakage.

자주 묻는 질문

How do I calculate heat recovered in an AHU?

Use Q_rec equals rho times c_p times airflow times effectiveness times the temperature difference, with rho 1.2 and c_p 1005, converting cubic metres per hour to cubic metres per second.

Should I maximize effectiveness?

Not always. Higher effectiveness often means more pressure drop and fan energy, so optimize the trade-off rather than chase the highest number.

What fan-power formula applies?

Fan power equals pressure drop times airflow divided by fan efficiency. Balance this against the heat recovered when choosing a core.

How do I verify installed performance?

Measure the actual supply temperature rise and pressure drop and compare them to the calculation. Trend for fouling or bypass leakage.

적합한 열교환기 선정

당사 엔지니어가 풍량, 온도, 압력 손실 예산에 맞춰 코어를 설계하고, 적용에 따라 판형·회전식·히트파이프 회수를 선택합니다. 다음을 읽으세요: 열교환기 가이드 , 또는 사양 관련 문의를 주세요.

견적 요청

관련 제품

Air-to-Air Heat Exchanger

HVAC 및 환기용 판형·회전식·히트파이프 회수.

Plate Heat Exchanger

공기 및 액체용 대면적 고정 코어.

회전식 열회수 휠

대풍량용 고효율 에너지 회수.

Heat Pipe Heat Exchanger

청정 적용을 위한 수동적·완전 분리 유동.

관련 게시물

위에 검색어를 입력하고 Enter 키를 눌러 검색하세요. 취소하려면 ESC 키를 누르세요.

맨 위로
무료 열회수 계산기 및 사이징 도구