F5-F9 medium efficiency synthetic pocket bag air filter with galvanized steel header

1차 vs 중효율 vs 고효율 필터: 나란히 비교

The Three Tiers at a Glance

Primary (G1-G4) Medium (F5-F9) HEPA/ULPA (H10-H14+)
Removes Coarse dust, hair, fibres Fine dust, pollen, microbes Sub-micron, bacteria, most viruses
Initial ΔP 20-45 Pa 45-95 Pa 100-300 Pa
Life 3-6 months 6-12 months 1-3 years
비용 낮음 Medium 높음
Typical role Pre-filter Final or pre-HEPA Final in clean/critical spaces

How They Work Together

A sound design stacks them: G4 pre – F7/F9 medium – H13/H14 HEPA. The pre-filter shields the costly stages; the medium lifts IAQ; the HEPA guarantees cleanliness where it counts.

Picking Your Combination

  • Comfort HVAC: G4 + F7.
  • Health-care: G4 + F8 + H13 terminal.
  • Cleanroom: G4 + F9 + H14 (add U15 for ISO 3-4).

Browse our primary, medium 및 HEPA product guides for model-level specs.

.yc-spec-wrap{margin:36px 0 28px}
.yc-spec-wrap figure{margin:0 0 24px;text-align:center}
.yc-spec-wrap figure img{max-width:100%;height:auto;border:1px solid #e5e7eb;border-radius:8px}
.yc-spec-wrap figcaption{font-size:14px;color:#6b7280;margin-top:8px}
.yc-spec{width:100%;border-collapse:collapse;font-size:15px;margin:8px 0 16px}
.yc-spec th,.yc-spec td{border:1px solid #d1d5db;padding:9px 12px;text-align:left;vertical-align:top}
.yc-spec th{background:#1f3a5f;color:#fff}
.yc-spec tr:nth-child(even) td{background:#f8fafc}
.yc-note{font-size:14px;color:#6b7280;margin-top:4px}
.yc-thumb-row{display:flex;gap:16px;flex-wrap:wrap;margin:0 0 20px}
.yc-thumb-row figure{flex:1 1 240px;margin:0;text-align:center}

Product Line-up & Side-by-Side Specifications

Primary panel air filter G1-G4
Primary — panel / pocket (G1–G4)
Medium efficiency pocket bag air filter F5-F9
Medium — pocket / V-cell (F5–F9)
Deep-pleat HEPA air filter H10-H14
High — HEPA / ULPA (H10–H14)
매개변수 Primary G4 Medium F7 High-efficiency H13
표준 EN 779 / ISO 16890 Coarse EN 779 / ISO 16890 ePM1 EN 1822
효율 90–95% arrestance 80–90% (ePM1 50–65%) ≥ 99.95% @ MPPS
Position in the filtration train 1st stage — protects downstream filters 2nd stage — supply-air quality Terminal — cleanrooms, labs, operating theatres
Typical initial ΔP 45–70 Pa 95–130 Pa 200–250 Pa
Recommended final ΔP 150 Pa 250–300 Pa 450–600 Pa
Typical replacement interval 3–6 months 6–12 months 1–3 years (ΔP based)
Typical applications Outdoor-air and return-air pre-filtration in AHUs Offices, malls, food & pharma HVAC Hospitals, cleanrooms, coating booths, electronics

Rule of thumb: stage primary → medium → high efficiency in series, and let each stage reach its recommended final ΔP before replacement — this is what protects the more expensive stage behind it.

자주 묻는 질문

How are the three efficiency tiers distinguished?
They are separated by the particle size they capture and their efficiency: coarse G classes, fine F classes and HEPA H classes.

Which tiers suit a typical office?
A two-stage G4 pre-filter plus an F7 final filter covers general comfort ventilation in most offices.

Why are filters arranged in stages?
Staging lets each tier handle its own size band, protects the finer media and lowers the overall cost of filtration.

Does higher efficiency always mean higher pressure drop?
Usually, but modern media design narrows the gap, so balance energy use against the required level of cleanliness.

자주 묻는 질문

How are the three efficiency tiers distinguished?

They are separated by the particle size they capture and their efficiency: coarse G classes, fine F classes and HEPA H classes.

Which tiers suit a typical office?

A two-stage G4 pre-filter plus an F7 final filter covers general comfort ventilation in most offices.

Why are filters arranged in stages?

Staging lets each tier handle its own size band, protects the finer media and lowers the overall cost of filtration.

Does higher efficiency always mean higher pressure drop?

Usually, but modern media design narrows the gap, so balance energy use against the required level of cleanliness.

적합한 열교환기 선정

당사 엔지니어가 풍량, 온도, 압력 손실 예산에 맞춰 코어를 설계하고, 적용에 따라 판형·회전식·히트파이프 회수를 선택합니다. 다음을 읽으세요: 열교환기 가이드 , 또는 사양 관련 문의를 주세요.

견적 요청

관련 제품

Air-to-Air Heat Exchanger

HVAC 및 환기용 판형·회전식·히트파이프 회수.

Plate Heat Exchanger

공기 및 액체용 대면적 고정 코어.

회전식 열회수 휠

대풍량용 고효율 에너지 회수.

Heat Pipe Heat Exchanger

청정 적용을 위한 수동적·완전 분리 유동.

관련 게시물

위에 검색어를 입력하고 Enter 키를 눌러 검색하세요. 취소하려면 ESC 키를 누르세요.

맨 위로
무료 열회수 계산기 및 사이징 도구